The SIPART PS2 positioners are suitable for all applications. Designed as standard with IP66 or NEMA 4x degree of protection, they are resistant to even the most hostile environments. SIPART PS2 is also available with an explosion-proof enclosure with EExd IIC T4-T6 type of protection. 
By means of a regular partial stroke test, SIPART PS2 ensures that ESD valves (emergency shutdown) and other open/close automated valves remain movable in the event of an emergency. The attached solenoid valve can also be tested. 
SIPART PS2 is equipped with comprehensive diagnostics functions as standard. In order to provide advanced warning of expensive failures during operation, our positioners continuously check the actuator and valve.
Detail
Setpoint signal: 
0/4–20 mA analog, HART, PROFIBUS PA or Foundation Fieldbus protocol
Stroke range: 
3 mm to 200 mm 
0.1 inch (1/8”) to 7.9 inch (7.5”) (larger strokes on request) 
Slewing angle range: 
30° to 100° (larger slewing angles on request)
Ambient temperature: 
-30 °C to +80 °C (-22 °F to 176 °F) (other temperature ranges on request)
Required air quality:
Class 2 in accordance with ISO 8573-1
Max air bleed in settled state:
< 0.036 m3n/h (0.02 scfm)

Benefits
Standard Macrolon enclosure to IP66/NEMA  4x protection, with optional aluminum or 
stainless steel enclosure 
Versions with external non-contacting travel sensors 
High flexibility in the stroke range from 3 to 200 mm (0.1 to 7.9 inch) (more on request) 
Communication via PROFIBUS PA, Foundation Fieldbus or HART 
Intelligent diagnostics functions 
EEx d explosion-proof version